    AC Tonnage Calculator

    Enter the square footage and climate to get the air conditioner size in tons and BTUs, with the Manual S sizing window applied. Includes BTU, ton and kilowatt conversions.

    The space

    Conditioned floor area, not the lot.

    Convert BTU to tons

    3 tons · 10.55 kW · 10,551 watts

    Recommended AC size

    3.5tons

    42,000 BTU/h unit for a 40,000 BTU/h (3.33 ton) load

    Cooling load

    40,000

    BTU/h

    Exact tonnage

    3.33

    tons before rounding

    Sq ft per ton

    480

    Typical 500–600 here

    BTU per sq ft

    25

    after adjustments

    Manual S check

    3.5 ton is within the 95–115% Manual S window for a 3.33 ton load.

    Standard sizes and what they cover in a warm climate

    SizeBTU/hSq ft (average build)kW
    1.5 ton18,000667–7835.28
    2 ton24,000889–1,0437.03
    2.5 ton30,0001,111–1,3048.79
    3 ton36,0001,333–1,56510.55
    3.5 ton42,0001,556–1,82612.31
    4 ton48,0001,778–2,08714.07
    5 ton60,0002,222–2,60917.58

    Put these numbers on a professional estimate

    EstimateKit turns your pricing into good-better-best estimates customers can approve from their phone, then tracks the job and invoice. $49/month, 14-day free trial.

    Start free trial

    How AC tonnage is calculated

    A ton of cooling is 12,000 BTU per hour, the heat needed to melt a ton of ice in a day. To size a unit you estimate the house's peak cooling load in BTU/h, divide by 12,000, and round to a standard size the way ACCA Manual S allows: between 95% and 115% of the load.

    Tons = (sq ft × BTU per sq ft for the climate × insulation × sun) ÷ 12,000

    The base rate is the number that matters most. Hot climates need about 30 BTU per square foot, warm ones 25, the middle of the country 22, and northern states 15–18. Poor insulation adds 15%, good insulation takes off 12%, and heavy west sun adds 10%. This page assumes 8-foot ceilings, double-pane windows and a single story; the full load calculator lets you change all of those and gives you the heating load too.

    Bigger is not better

    An oversized air conditioner satisfies the thermostat in a few minutes and shuts off before the coil has pulled much moisture out of the air. The house ends up cool and sticky, the equipment cycles itself to death, and the customer calls you back. Right-sized equipment runs longer, quieter cycles and dehumidifies properly. When the load lands between sizes, go down, not up, unless a Manual J says otherwise.

    Quick conversions

    • 1 ton = 12,000 BTU/h = 3.517 kW of cooling
    • 1 kW = 3,412 BTU/h
    • 1.5 ton = 18,000 · 2 ton = 24,000 · 2.5 ton = 30,000 · 3 ton = 36,000 · 4 ton = 48,000 · 5 ton = 60,000 BTU/h
    • Nominal airflow is 400 CFM per ton; the CFM calculator covers the rest.

    Frequently asked questions

    What size AC do I need for a 2,000 square foot house?

    About 3 tons in a mixed climate, 3.5 to 4 tons in a hot climate like Texas or Florida, and 2.5 tons in the northern states, assuming average insulation. Poor insulation, lots of west-facing glass or vaulted ceilings can push each of those up half a ton.

    How many square feet will a 3-ton AC cool?

    Roughly 1,200–1,500 square feet in a hot climate, 1,600–2,000 in a mixed climate, and up to 2,400 in a cool climate with good insulation. The table on this page shows the range for the climate you selected.

    How do I convert BTU to tons?

    Divide BTU per hour by 12,000. A 36,000 BTU unit is 3 tons; a 24,000 BTU unit is 2 tons. Type any BTU figure into the converter above to see tons, kilowatts and watts.

    Can I use the model number to find tonnage?

    Usually. Most manufacturers put the nominal BTU in the model number in thousands: 24 means 24,000 BTU or 2 tons, 36 means 3 tons, 48 means 4 tons, 60 means 5 tons. Check the data plate to confirm.

    Is a half-ton oversize acceptable?

    Manual S allows cooling equipment up to 115% of the load, so a half-ton over on a 3-ton load (117%) is just outside the window and a half-ton over on a 4-ton load (112%) is inside it. Heat pumps in cold climates get more latitude because the heating load usually governs.