Free · Refrigerant charging

    Superheat & Subcooling Calculator

    Pick the refrigerant, type your gauge pressures and line temperatures, and get superheat, subcooling and a charge verdict against the target. PT charts for R-410A, R-454B, R-32, R-22 and R-134a are built in.

    Suction side (superheat)

    Clamp the probe 6 in. from the service valve, insulated, after 15 minutes of run time.

    Liquid side (subcooling)

    Metering device

    Use the outdoor unit's data plate. 8–12°F is typical when it is missing.

    Subcooling

    9.9°F

    Target 10°F from the nameplate.

    On target

    Within ±3°F of the 10°F nameplate target. Charge is correct.

    Superheat

    12.4°F

    Sat 39.6°F at 118 psig

    Subcooling

    9.9°F

    Sat 99.9°F at 318 psig

    Evap saturation

    39.6°F

    Saturated

    Cond saturation

    99.9°F

    Saturated

    R-410A pressure-temperature chart

    Saturation pressure at sea level. Values between rows are interpolated in the calculator.
    °Fpsig
    -4010.8
    -3017.8
    -2026.3
    -1036.5
    048.4
    1062.4
    2078.7
    3097.4
    40118.8
    50143.1
    60170.7
    70201.7
    80236.5
    90275.3
    100318.5
    110366.5
    120419.5
    130478.0
    140542.6
    150613.9

    Turn the repair into a signed ticket

    EstimateKit builds the repair estimate on your phone, gets the customer's signature, and invoices the job when you close the panel. $49/month, 14-day free trial.

    Start free trial

    How to read superheat and subcooling

    Superheat is how many degrees the suction vapor is above its saturation temperature. It tells you the evaporator is fully boiling off the refrigerant and no liquid is heading to the compressor. Subcooling is how many degrees the liquid leaving the condenser is below its saturation temperature. It tells you there is a solid column of liquid feeding the metering device.

    Superheat = suction line temp − saturation temp at suction pressure
    Subcooling = saturation temp at liquid pressure − liquid line temp

    The calculator converts gauge pressure to saturation temperature from the PT chart above, then subtracts. Fixed-orifice systems (pistons and capillary tubes) are charged to a target superheat that moves with conditions. TXV and EEV systems hold superheat on their own, so they are charged to the subcooling on the data plate.

    Target superheat for fixed-orifice systems

    Target SH = ((3 × indoor wet bulb) − 80 − outdoor dry bulb) ÷ 2

    This is the field approximation of the manufacturer's charging chart. It needs a real wet bulb reading from the return air, not a guess. When the result drops under 5°F the chart says the conditions are too cold to charge accurately; wait for a warmer day or weigh the charge in.

    Before you add or remove refrigerant

    1. Run the system at least 15 minutes with the indoor temperature near normal.
    2. Confirm airflow first: clean filter, coil, blower speed and a temperature split near 18–22°F. Half of "low charge" calls are airflow.
    3. Take line temperatures with a clamp probe, insulated, on clean copper 6 in. from the service valve.
    4. Charge in small steps and let readings settle for 5–10 minutes between them.

    R-454B and R-32 notes

    Both are A2L refrigerants, so use A2L-rated gauges, recovery equipment and leak detectors. R-454B is a blend with about 1.5°F of glide: the calculator uses the dew point for superheat and the bubble point for subcooling, which is how the manufacturer charts are published. R-32 is a single-component refrigerant with no glide. Neither is a drop-in for R-410A.

    Pricing the repair? Run the numbers through the service call pricing calculator before you write the ticket.

    Frequently asked questions

    What should superheat be on an R-410A system?

    On a fixed-orifice system the target moves with indoor wet bulb and outdoor temperature, typically 5–25°F. On a TXV system superheat should sit around 8–14°F at the evaporator and you charge to subcooling instead. Always use the target from the manufacturer's chart or nameplate when you have it.

    What is a normal subcooling reading?

    Most residential TXV systems specify 8–12°F of subcooling at the outdoor unit. The exact number is on the data plate or the installation manual. Readings 3°F or more off the target usually mean the charge is off, but check for restrictions and non-condensables before adding refrigerant.

    Why does the calculator say the pressure is out of range?

    Each refrigerant's PT table covers a fixed range, roughly −20°F to 130°F saturation. A pressure outside that range usually means the wrong refrigerant is selected or the gauge is reading a different port. R-32 and R-454B run higher than R-410A at the same temperature; R-22 and R-134a run much lower.

    Does the R-454B glide matter for charging?

    Slightly. R-454B has about 1.5°F of temperature glide, so superheat uses the dew-point column and subcooling uses the bubble-point column. The calculator does that automatically when R-454B is selected. Manufacturer charging charts for R-454B are published the same way.

    Can I charge by superheat on a TXV system?

    No. A TXV adjusts to hold its own superheat, so superheat only tells you whether the valve is working. Charge a TXV system to the nameplate subcooling and use superheat as a check that the valve is not stuck or starved.

    Complete business software for HVAC contractors. Estimates, customers, jobs, and invoicing — all in one platform.

    hello@estimatekit.com
    PhoenixHoustonDallasMiamiAtlantaLas VegasLos AngelesTampaSan AntonioAustin